Calibrating RCDT - Residual Current Device Testers
According to the QLD Electrical Safety Act
2002 - Section 18 - (2)(b) : if a testing instrument can not be visually confirmed as being
correctly functioning and safe — that the instrument is tested at least every 6 months to
ensure it is in proper working order.
RCD Current
measurement
RDC Tests Phase Start Angle
RCD Trip Time Measurement
RCD Current Duration Measurement Line Voltage Measurement
RCD (Residual Current Devices) operate by sensing when a current flow in the live and neutral
conductors within an installation are not equal and opposite. Any imbalance implies that an additional
current path exists, typically through the earth due to excessive leakage or fault
situation.
RCD testers are designed to simulate a range of fault currents, and to time the operation of the
device. This will indicate the ability of the RCD to interrupt a particular fault current within the
specified time limits to ensure protection against electrocution, fire or damage. Calibration ensures that a
tester complies to its manufacturers specifications and can accurately test an RCD for a Pass / Fail
result.
Ensure your equipment is in specification so that the RCD testing you do is conducted
in accordance with AS/NZS 3760 "In-service safety inspection and testing of electrical equipment" and AS/NZS
3190 "Approval and test specification – Residual current devices (current-operated earth-leakage
devices)"
All measurements are traceable to national and international
standards via a registered NATA laboratory or a mutually recognised international testing authority. (See
NATA’s International Activities )
|